Outdoor Voltage Transformers with Cycloaliphatic Cast Resin Insulation 12 - 36 kV
The voltage transformers series EGF (single-pole insulated) and ZGF (double-pole insulated) are maintenance-free cast-resin transformers for outdoor application and system voltage Um up to 36 kV. They comply with various national and international standards (IEC 60044-2, VDE 0414, DIN 42600, ÖVE-P20, ANSI, GOST etc.).
The Voltage Transformers are designed for ambient temperatures from -40°C up to +50°C and for operation up to 1000m above sea level (>1000m on request).
Single-Pole Insulated Voltage Transformers:
- secondary 100/√3 V or 110/√3 V
- accuracy classes 0.2, 0.5, 1, 3, 3P and 6P
- winding for earth-fault detection on request (100/3 V or 110/3 V)
- voltage factor 1.9 x Un for 8 hours
- frequency 50 Hz or 60 Hz
Double-Pole Insulated Voltage Transformers:
- secondary 100 V oder 110 V
- accuracy classes 0.2, 0.5, 1, 3
- voltage factor 1.2 x Un or 1.5 x Un
- frequency 50 Hz or 60 Hz
Our instrument transformers can be delivered in a calibratable design for metering purposes. Type approvals for calibration are available for several countries.
We also produce current and voltage transformers in special designs and specification - we are looking forward to your inquiry!
| Transformer Type |
System Voltage (Um) |
Insulation level |
thermal limiting output |
Max Output Cl. 0,2 |
Max Output Cl. 0,5 |
Max Output Cl.1 |
Creepage distance |
Weight |
| KV rms | KV rms/KV | VA | VA | VA | VA | mm | Kg | |
| EGF10 | 12 | 28/75 | 400 | 30 | 90 | 180 | 760 | 40 |
| ZGF10 | 12 | 28/75 | 400 | 30 | 90 | 180 | 980 | 42 |
| EGF20 | 24 | 50/125 | 600 | 30 | 90 | 180 | 900 | 48 |
| ZGF20 | 24 | 50/125 | 600 | 30 | 90 | 180 | 1120 | 50 |
| EGF30 | 36 | 70/170 | 800 | 50 | 120 | 200 | 1040 | 54 |