Indoor Voltage Transformers 12 - 36 kV
The Voltage Transformers series EGS / EGG / EY (single-pole insulated) and ZGS / ZGG (double-pole insulated) are maintenance-free cast-resin transformers for indoor application for system voltage Um up to 36 kV. They comply with various national and international standards (IEC 60044-2, VDE 0414, DIN 42600, ÖVE-P20, ANSI, GOST etc.).
Single-Pole Insulated Voltage Transformers:
- secondary 100/√3 V or 110/√3 V
- accuracy classes 0.2, 0.5, 1, 3, 3P and 6P
- winding for earth-fault detection on request (100/3 V or 110/3 V)
- voltage factor 1.9 x Un for 8 hours
- frequency 50 Hz or 60 Hz
- EGS10/S and EGS20/S can be equipped with primary fuse
Double-Pole Insulated Voltage Transformers:
- secondary 100 V oder 110 V
- accuracy classes 0.2, 0.5, 1, 3
- voltage factor 1.2 x Un or 1.5 x Un
- frequency 50 Hz or 60 Hz
Our instrument transformers can be delivered in a calibratable design for metering purposes. Type approvals for calibration are available for several countries.
We also produce current and voltage transformers in special designs and specification - we are looking forward to your inquiry!
| Transformer Type | System Voltage (Um) | Insulation Level | thermal limiting output | Max. Output Cl. 0,2 | Max. Output Cl. 0,5 | Max. Output Cl. 1 | Weight |
|
KV rms
|
KV rms/KV
|
VA
|
VA
|
VA
|
VA
|
Kg
|
|
| EGS 10 |
12
|
28/75
|
400
|
30
|
90
|
180
|
14
|
| EGS 10/S |
12
|
28/75
|
400
|
30
|
90
|
180
|
18
|
| EGS 20 |
24
|
50/125
|
600
|
30
|
90
|
180
|
26
|
| EGS 20/S |
24
|
50/125
|
600
|
30
|
90
|
180
|
31
|
| EGG 20 |
24
|
50/125
|
600
|
50
|
120
|
200
|
47
|
| EGS 30 |
36
|
70/170
|
800
|
50
|
120
|
200
|
61
|
| ZGS 10 |
12
|
28/75
|
400
|
30
|
50
|
180
|
14
|
| ZGS 20 |
24
|
50/125
|
600
|
30
|
50
|
180
|
26
|
| ZGG 20 |
24
|
50/125
|
600
|
50
|
120
|
200
|
46
|
| ZGS 30 |
36
|
70/170
|
800
|
50
|
120
|
200
|
60
|